Ridge Vent Calculator

Work out how many linear feet of ridge vent the exhaust half of the attic requirement needs, from the attic area, the ventilation ratio and the product's net free area per foot — and whether your ridge is long enough to take it.

Quick answer: a 1,200 sq ft attic at 1:150 needs 1,152 sq in of net free area, so 576 sq in of exhaust. At 18 sq in per foot that is 32 ft of ridge vent, which fits a 40 ft ridge with 8 ft to spare — eight 4 ft sections, plus 12 soffit vents to balance the intake. At 9 sq in per foot the same attic needs 64 ft — and it no longer fits.

  • Linear feet from NFA
  • Ridge length check
  • Exhaust share editable

Ridge vent calculator inputs and results

Usable ridge excludes hips, valleys and any section too close to a gable end to vent.

Net free area per soffit vent from the product data. A 16 × 4 in vent is usually around 50 sq in.

Most ridge vents are sold in 4 ft or 8 ft sections.

Intake and exhaustridge exhaustsoffit intakesoffit
Air enters at the soffit intake and leaves at the ridge exhaust; both are needed for the ratio. → ridge vent needed
Ridge vent needed
32 ft
576 sq in of exhaust at 18 sq in/ft
Total NFA
1,152 sq in
Exhaust NFA
576 sq in
Intake needed
576 sq in
Fits the ridge?
Yes
Ridge vent sections
8
Soffit vents needed
12
Intake vent area
4.0 sq ft
Spare ridge length
8.0 ft

The fit check compares the vent length needed with the ridge you have; intake is half the total and is often the missing piece.

Show calculation

What this ridge vent calculator works out

Ridge vent is bought and installed by the linear foot, but the requirement is written in square inches of net free area. This calculator bridges the two: it works out the exhaust half of the requirement, then converts it into the length of vent that provides it. It also compares that length with the ridge you actually have, because on a hip roof or a small plan the ridge is often shorter than the calculation wants.

Two things decide the answer more than anything else, and neither is obvious from the arithmetic. The net free area per foot of the product varies by more than a factor of two between ridge vents, which changes the required length in proportion. And the ridge you can actually vent is usually less than the building length, because hips, valleys, chimneys and dormers interrupt it.

What it does not do: it does not size the intake, and it does not tell you whether the ridge vent suits your covering. Both are separate questions with their own sections. The full passive requirement across the roof is in the roof ventilation requirements calculation.

A continuous ridge vent running along the top of a shingled roof ridge, with cap shingles over the vent profile.
A continuous ridge vent provides exhaust along the whole ridge rather than at a few points.
Exhaust needs intake. Fitting 32 ft of ridge vent without matching soffit intake does not ventilate the attic; it depressurises it. The page reports the intake figure you need to match, but not the product to do it.

What each ridge vent input and result means

Five inputs, nine results. Two describe the attic, one describes the product, two describe the roof you have, and four turn the requirement into the parts you actually order.

The five inputs.
FieldUnitWhat to enter
Attic floor areasq ftLength times width of the attic floor. The ratio is written against floor area, not roof area.
Ventilation ratio1:150 or 1:3001:150 unless you genuinely meet the conditions for the reduction — which include a balanced high-and-low arrangement.
Exhaust sharepercentUsually 50%. The high vents take half and the low intake takes the rest, which is why the intake figure is reported alongside.
Net free area per footsq in/ftThe product's rated figure. This is the single most important input on the page — see the section below on why it varies so much.
Ridge length availablefeetThe run you can actually vent, not the building length. Subtract hips, valleys, chimneys and anything else that interrupts the ridge.
The nine results.
ResultUnitWhat it means
Total NFAsq inThe whole requirement, both sides. The figure a code check is written against.
Exhaust NFAsq inThe share the ridge has to provide, at your exhaust percentage.
Ridge vent neededfeetExhaust NFA divided by the product rating. The length you order.
Intake neededsq inWhat the low vents have to provide to balance it. Report only — the soffit calculator sizes the products.
Fits the ridge?yes / noWhether the required length is available on your roof. A "no" means the ridge cannot be the only exhaust.
Ridge vent sectionscountThe required length divided by the section length you buy, rounded up. Sections are sold in fixed lengths, so this is the number that goes on the order.
Soffit vents neededcountThe intake area divided by the net free area of one soffit vent, rounded up. Whole vents only, so the installed intake is normally slightly above the target.
Intake vent areasq ftThe intake requirement converted to square feet, so it can be compared with the soffit area you have rather than with a product rating.
Spare ridge lengthftRidge available minus ridge required. Negative means the ridge is too short and the shortfall has to come from a second exhaust type.

Areas are in square inches and lengths in feet. The ridge length is shown to one decimal place, because ordering is usually rounded to the nearest stock length or to whole sections.

How to use the ridge vent calculator

Sizing the exhaust half of the ventilation ratio, as a length of ridge.

  1. Enter the attic. Give the attic floor area and the ventilation ratio.
  2. Enter the product. Give the net free area per foot of the ridge vent.
  3. Set the share. Enter the proportion of the exhaust this ridge is providing if it is not the only outlet.
  4. Read the length. The result gives the length required and whether it fits the ridge available.

Ridge vent length formulas

total NFA (sq in) = attic sq ft ÷ ratio × 144
exhaust NFA = total × exhaust share ÷ 100
ridge length (ft) = exhaust NFA ÷ vent rating per ft
intake NFA = total − exhaust NFA
sections = ⌈ridge length ÷ section length⌉
soffit vents = ⌈intake NFA ÷ soffit NFA each⌉
intake area (sq ft) = intake NFA ÷ 144
spare ridge = ridge available − ridge length

The 144 converts square feet of vent area into square inches, because vent products are rated in square inches while the code ratio is expressed in square feet.

Ridge vent net free area per foot is the input that decides the length

Two ridge vents can look similar on a roof and differ by more than a factor of two in the air they pass. The rating is published as net free area per linear foot, and it depends on the internal baffle design, the profile height and how much of the opening the filter or mesh occupies.

Published figures across the industry run from roughly 9 to 20 sq in per foot. That range is the whole calculation: for the same 576 sq in of exhaust, a vent rated at 20 needs 29 ft, and one rated at 9 needs 64 ft.

The same attic exhaust requirement at different product ratings. 1,200 sq ft attic at 1:150, 50% exhaust, 576 sq in required.
RatingRidge vent neededFits a 40 ft ridge?
20 sq in/ft28.8 ftYes, 11 ft spare
18 sq in/ft32.0 ftYes, 8 ft spare
13.5 sq in/ft42.7 ftNo — short by 2.7 ft
9 sq in/ft64.0 ftNo — short by 24 ft

The rating is usually quoted at a standard test pressure. In service, a baffle clogged with debris or a vent partly sealed by cap shingles passes less than its rating, so the installed figure is a ceiling rather than a floor.

The practical consequence is that the product choice is a design decision, not a shopping decision. A low-profile vent that sits neatly under the cap shingles may need half again the length of a taller one — and if the ridge is short, that difference decides whether the ridge can be the only exhaust at all.

If you want to work the other way and check the net free area a given length of a specific product provides, the ridge vent NFA calculation runs it in that direction.

Worked ridge vent examples

Example 1 — 1,200 sq ft attic at 1:150, 18 sq in/ft

Total NFA
1,200 ÷ 150 × 144 = 1,152 sq in
Exhaust at 50%
576 sq in
Ridge length
576 ÷ 18 = 32 ft
Against a 40 ft ridge
fits, with 8 ft to spare
Ridge sections (4 ft each)
32 ÷ 4 = 8
Soffit vents at 50 sq in each
576 ÷ 50 = 11.52 → 12
Intake vent area
576 ÷ 144 = 4.00 sq ft
ridge length = (1,200 ÷ 150 × 144 × 0.5) ÷ 18 = 32 ft

Example 2 — the same attic at 1:300

Total NFA
1,200 ÷ 300 × 144 = 576 sq in
Exhaust at 50%
288 sq in
Ridge length
288 ÷ 18 = 16 ft

Half the vent, half the ridge. Whether the reduced ratio is permitted depends on the conditions in the code, not on the arithmetic.

ridge length = (1,200 ÷ 300 × 144 × 0.5) ÷ 18 = 16 ft

Example 3 — the same attic with a low-rated vent

Inputs
1,200 sq ft, 1:150, 50% exhaust, 9 sq in per foot, 40 ft ridge
Exhaust needed
576 sq in
Ridge vent needed
576 ÷ 9 = 64.0 ft
Ridge available
40 ft
Shortfall
24 ft — the ridge cannot do it alone

Same attic, same requirement, and a completely different conclusion — decided entirely by the product rating. With 64 ft needed on a 40 ft ridge, the ridge vent can supply at most 360 sq in and the remaining 216 has to come from somewhere else.

That is what the "fits the ridge?" result is for. When it says no, the options are a higher-rated product, a second exhaust type, or accepting that the ridge is only part of the system — which is exactly the comparison the gable vs ridge vent estimator is built for.

ridge length = 576 ÷ 9 = 64 ft on a 40 ft ridge

Ridge vent calculator limitations

  • Every foot of vent is rated the same. Net free area per linear foot is taken as constant along the run. Where a profile changes at a hip or a valley, the rating changes with it and the blended figure has to be entered by hand.
  • No airflow modelling. Distribution, baffles, truss webs and anything stored against the deck all throttle a vent in service. The arithmetic sizes the opening, not the airflow through it.
  • The ratio is an input, not a verdict. The general rule is 1:150. The reduction to 1:300 is conditional — it turns on a Class I or II vapour retarder on the warm side of the ceiling and on a balanced high-and-low arrangement. Local amendments move both numbers, so confirm the ratio your jurisdiction enforces before you order vent.
  • Fifty percent is a design choice, not a code figure. The upper-vent share the code permits is a band rather than a single value, and half sits at the top of it. A roof built to the bottom of that band needs less ridge vent and more intake than this page returns.
  • Ridge length means vented length. Hips, chimneys, valleys and skylights all interrupt the ridge. The figure to enter is the sum of the runs you can actually vent — not the building length, and not the ridge measured on a plan where the interruptions are not yet drawn.
  • Intake is not converted. The intake figure is reported so the balance is visible, but it is not turned into a product length. That conversion depends on the soffit detail, and the soffit vent intake calculator handles it.
  • No check that the intake exists. Soffit vents get blocked by insulation, painted shut, or left out altogether. A correct exhaust figure over a dead intake ventilates nothing, and this page cannot see any of that.
  • Air sealing is outside the scope. Sealing the ceiling plane matters as much as the vent area. No amount of ridge vent compensates for an attic that is open to the house through recessed lights and top plates.
Ridge cap shingles being fixed along a roof ridge over a vent strip.
The cap shingles sit over the vent, so the profile height and nailing pattern both matter.

Continuous ridge vent length: same rating, measured in feet

A continuous ridge vent is not a different calculation from a sectional one. Both are rated in net free area per linear foot, and both are sized by dividing the exhaust requirement by that rating.

The practical difference is coverage. A continuous vent runs the whole ridge as one profile, so its net free area is spread evenly along the ridge line. Sectional vents are discrete units, and the gaps between them provide no exhaust at all.

That matters when the ridge is short. A 20 ft ridge fitted with a continuous vent provides exhaust along all 20 ft; the same ridge fitted with four 2 ft sections provides exhaust over 8 ft and nothing over the remaining 12 ft.

Where a manufacturer quotes a single rating for a continuous product, enter it directly. Where the ridge is interrupted by hips or a chimney, measure only the vented runs and add them together before entering the length.

One thing to keep straight when ordering: the vent, the ridge cap over it and the fixing system beneath are three separate components. A dry-fixed dry ridge system and a vented ridge are not interchangeable, and a vent profile that suits one covering may not suit another. The length this page returns is the vent only.

Frequently asked questions

Divide the exhaust net free area you need by the vent's rating per linear foot. A 1,200 sq ft attic at 1:150 needs 1,152 sq in in total, so 576 sq in on the exhaust side; at 18 sq in per foot that is 32 ft of ridge vent. The rating per linear foot is printed in the product literature and varies between profiles.

Because ventilation is a flow path. The code ratio applies to the total net free area, and the usual design splits it evenly between low intake at the eaves and high exhaust at the ridge. If the ridge alone provided the whole requirement, there would be no defined intake and the system would pull air through ceiling gaps instead.

Yes. A continuous ridge vent can only be as long as the ridge. If the calculated length exceeds the available ridge, the shortfall has to come from another exhaust type such as box vents. This calculator shows both the required length and whether your ridge is long enough.

It is the open area, after the baffle and filter, that one foot of vent provides, quoted in square inches. A profile rated at 18 sq in/ft provides 216 sq in over a 12 ft ridge. It is never the same as the physical opening, which is larger.

Too much exhaust relative to intake is the problem, not the vent itself. Oversized exhaust depressurises the attic and draws conditioned air through the ceiling. Match the intake first, then increase both sides together.

Only along the ridge; the hips cannot take a ridge vent. A hip roof usually has a shorter ridge relative to its plan area, which makes the available length a real constraint. That is often where box vents or a powered option becomes necessary.

Rated ridge vents use an internal baffle and filter to resist wind-driven rain and snow. Performance depends on the profile and on the roof pitch. Follow the manufacturer's slope limits; some products are not approved below a certain pitch.

A continuous ridge vent distributes exhaust along the whole ridge, which usually gives more uniform airflow than a few discrete vents. Box vents are simpler and cheaper where the ridge is short. The ratio check tells you whether the total is enough once you have chosen.

Not the net free area, but it can change which products are approved. Some ridge vents have a minimum pitch, and airflow behaviour at very shallow pitches differs. Check the product's installation limits against your roof.

Three routes, in rough order of preference. First, confirm which ratio actually applies — moving from 1:150 to 1:300 halves the exhaust requirement, which often closes the gap on its own. Second, pick a profile with a higher rating per foot, since the same ridge then delivers more area. Third, make up the shortfall with box vents or another exhaust type. Adding a second exhaust type is legitimate; running an oversized continuous vent over a short intake is not.

You can, but they stop behaving as intake and start competing with the ridge. Gable vents sit high on the wall, close to the ridge in elevation, so the ridge can draw air straight across from them instead of pulling it up from the eaves. The result is a short circuit: the numbers balance on paper while the lower attic stays still. If a ridge vent is added, the gable vents are normally closed off and the intake is moved down to the soffit.

It halves the total vent area, and therefore the exhaust half with it. On the 1,200 sq ft attic used above, 1:300 gives 576 sq in total instead of 1,152, so 288 sq in on the ridge — 16 ft at 18 sq in per foot rather than 32 ft. The catch is that 1:300 is not a free upgrade: it depends on a qualifying vapour retarder and on the high-and-low balance being met. If either condition fails, the roof is back to 1:150 and the longer figure stands.

Divide the intake net free area by the net free area of one vent. A 1,200 sq ft attic at 1:150 needs 576 sq in of intake, so vents rated at 50 sq in each come to 12. Always round up, and check the product data: a 16 × 4 in soffit vent is usually around 50 sq in, but a 16 × 8 in vent is closer to 65 to 100 sq in, which changes the count.

Divide the required length by the section length and round up: 32 ft of ridge vent at 4 ft sections is 8 pieces. Add one spare section for cuts and for the short runs at each end, because offcuts from the ridge rarely fit anywhere else.

Where these numbers come from

The ratio and its exceptions come from the attic ventilation provisions of the residential code. The vent rating comes from the product literature, which states net free area per linear foot. Neither is a substitute for the adopted code in force where the roof is being built.

The requirement this page works to is IRC R806.2: net free ventilating area of not less than 1/150 of the area of the space ventilated, reducible to 1/300 where the specified conditions are met, including a qualifying vapour retarder and a balanced high-and-low vent arrangement. It sits in Chapter 8 of the International Residential Code. This page states the ratio rather than reproducing the section, and your jurisdiction may amend it.

The split between intake and exhaust is treated here as an even one. That is a working assumption for sizing, not a code value, and the upper-vent share the code allows is a band rather than a fixed percentage.

  • International Code Council, International Residential Code, Chapter 8 — attic ventilation provisions.
  • Ridge vent manufacturer data for net free area per linear foot and approved roof slopes.
  • Ventilation guidance on the relationship between intake area and exhaust performance.

Sizing the intake to match?