Scupper Drain Sizing Calculator

Size a parapet scupper as a weir: peak flow, head of water and a coefficient give the opening width, checked against a practical minimum.

Quick answer: 6,000 sq ft at 4 in/hr produces about 237 gpm. Split across 2 scuppers with 4 in of head, each opening needs to be 5.5 in wide — wider than the 4 in practical minimum, so 5.5 in governs.

  • Weir flow through a rectangular opening
  • Hydraulic width against practical minimum
  • Flow per opening

Scupper sizing inputs and results

Head is the depth of water the roof can hold before it reaches a threshold or upstand, which is a building decision.

Opening on the roof planeopening widthcurb heightroof plane
Measure the opening width and the curb height at the opening itself. → opening width required
Opening width required
5.5 in
hydraulic width governs · 5.5 in > 4.0 in minimum
Peak flow
236.9 gpm
Flow per scupper
118.4 gpm
Hydraulic width
5.5 in
Governing
Hydraulic

A clear opening is assumed; debris cuts capacity, which is why several openings beat one large one.

Show calculation

A scupper is a weir, not a hole sized by eye

A scupper is not a hole sized by eye. It is a weir, and the water passing through it depends on the width of the opening, the depth of water standing against it, and the shape of the edge — in a very non-linear way.

This page takes the peak flow from the catchment and divides it between the openings you intend to build. It then solves the weir equation for the width each opening needs at the head you specify, and compares that against a practical minimum width so a hydraulically adequate but unbuildable slot does not come out as the answer.

The output is a single number to build to, plus the two inputs that produced it, so you can see whether the width or the minimum is driving the result.

A rectangular scupper opening formed through a roof parapet wall, with the roof surface behind it.
A scupper is a weir in a wall. Its capacity depends on the depth of water behind it, not only on its size.

The seven inputs and five results

Seven fields go in. Three describe the water, two describe the openings, and two are the coefficients and limits that decide the answer.

InputUnitWhat it isHow to obtain it
Catchment areasq ftPlan area draining to the scuppersMeasured from the roof plan, not the sloped surface
Rainfall intensityin/hrDesign storm rate for the siteA local design chart or drainage authority
Runoff coefficient—Share of rainfall that becomes runoff0.95 for a membrane roof; lower for ballast or planting
Number of scupperscountHow many openings share the flowYour layout — and more is better, for the reason in the debris section
Head above invertinDepth of water standing against the openingA building decision: the threshold, upstand or flashing level the water may reach
Weir coefficient—Discharge coefficient for the edge shape3.0 for a sharp-edged opening; higher for a rounded one
Practical minimum widthinThe narrowest opening worth buildingYour judgement or a local requirement — below it the slot blocks

All seven are entered on the left of the calculator, and the result updates as you type.

The five results

Two describe the flow, two describe the opening, and one says which of them decided the answer.

ResultUnitWhat it means
Peak flowgpmWhat the catchment delivers at that intensity. A property of the roof and the weather.
Flow per scuppergpmPeak flow divided between the openings.
Hydraulic widthinThe width the weir equation says each opening needs at that head.
Opening width requiredinThe larger of the hydraulic width and your practical minimum. The figure to build to.
Governing—Whether the hydraulic width or the practical minimum set the answer.

The governing line is the useful one: it tells you whether to change the head, the count, or neither.

The catchment and the head

One of these is measured and one is decided, and the one that is decided has far more influence on the answer.

The catchment

Take the plan area that drains to these scuppers. On a flat roof that is the footprint of the contributing area, with no pitch factor to apply; where the roof falls to more than one outlet, measure each catchment separately.

The flow itself is what the stormwater runoff calculation returns from the same inputs. This page takes that flow and turns it into an opening width.

The head

The head is the depth of water the roof is allowed to hold before it reaches something that matters — a door threshold, a rooflight upstand, the top of the flashing, or the top of the parapet itself.

That makes it a building decision rather than a hydraulic one. A deeper head gives a narrower scupper, but it also means more weight on the roof and a greater chance of water finding a weakness in the waterproofing. The opening is sized once that decision is made.

The number of openings

The count divides the flow, so two scuppers each carry half. It also decides what happens when one blocks, which is the case a scupper is most likely to face.

Two openings that each carry half the flow still work when one is blocked, at double the head. One opening sized for the whole flow has nothing to fall back on.

Common measuring mistakes

  • Sloped area used as catchment. On a flat roof there is no pitch factor, and applying one overstates the flow.
  • Head taken as the parapet height. It is the depth to the lowest point water must not reach, which is often lower.
  • One scupper for the whole roof. The count is a resilience decision as much as a hydraulic one.
  • Practical minimum set to zero. A hydraulically correct 1 in slot is unbuildable and blocks immediately.
  • Weir coefficient left at 3.0 for a rounded edge. A well-formed opening carries more, and the coefficient is where that shows.

How to use the Scupper Drain Sizing Calculator

A scupper is a weir, so the depth of water matters more than the width.

  1. Enter the catchment. Give the area draining to the scuppers, with intensity and runoff coefficient.
  2. Set the openings. Enter how many scuppers share the flow.
  3. Set the head. Enter the depth of water the roof can hold before it reaches a threshold or upstand.
  4. Read the width. The result gives the hydraulic width and takes the larger of that and your practical minimum.

If the governing line says the practical minimum is deciding it, the hydraulics are not the constraint — build the minimum and move on. If it says the hydraulic width governs, the head or the count is what to change.

How the opening width is solved

flow (gpm) = coefficient × intensity × area × 0.01039
flow per scupper = flow ÷ number of scuppers
flow (cfs) = flow per scupper ÷ 448.831
width (ft) = flow (cfs) ÷ ( Cw × head (ft)1.5 )
width (in) = width (ft) × 12
governing width = max(hydraulic width, practical minimum)

Variables

A
Catchment plan area draining to the scuppers, in square feet.
I
Rainfall intensity for the design storm, in inches per hour.
C
Runoff coefficient, dimensionless.
Cw
Weir coefficient for the edge shape — 3.0 for a sharp-edged opening.
H
Head of water standing against the opening, in feet once converted from inches.
L
Opening width, in feet. The calculator solves for this and reports it in inches.

Unit explanation

The weir equation is Q = Cw × L × H3/2, with Q in cubic feet per second and both L and H in feet. Rearranging for L gives the fourth line, which is why the head is divided by 12 before use and the result multiplied by 12 at the end.

The constant 448.831 converts US gallons per minute to cubic feet per second, and 0.01039 converts rainfall depth over an area into gallons per minute. Both are arithmetic, not assumptions. A weir coefficient of 3.0 is dimensionally consistent only in US customary units; in SI the equivalent figure is about 1.84.

Why the exponent is 1.5

The equation comes from flow over a sharp crest: the velocity of water leaving the crest rises with the square root of the depth, and the flow area rises with the depth itself. Multiplying the two gives depth to the power of one and a half.

That single exponent is why head is the stronger lever. Doubling the head multiplies capacity by 2.83, while doubling the width only doubles it.

Why the practical minimum is applied last

The weir equation does not know whether an opening can be built or kept clear. At a small head it will happily return a width of an inch or less, which is hydraulically correct and practically useless.

Taking the larger of the two figures is therefore a deliberate override: the hydraulic width is the minimum the water needs, and the practical minimum is the smallest that will still work after a season of debris.

Numerical example

4,000 sq ft at 5 in/hr, coefficient 0.9, three scuppers, 3 in of head, Cw = 3.0 and a 4 in practical minimum:

Peak flow
0.9 × 5 × 4,000 × 0.01039 = 187.0 gpm
Per scupper
187.0 ÷ 3 = 62.3 gpm
In cfs
62.3 ÷ 448.831 = 0.1389 cfs
Head
3 in = 0.25 ft, so H1.5 = 0.125
Width
0.1389 ÷ (3.0 × 0.125) = 0.3704 ft
In inches
0.3704 × 12 = 4.44 in
Governing
max(4.44, 4.0) = 4.44 in, hydraulic width governs

A 4.44 in opening is buildable, so the hydraulic result stands. Had the head been 2 in instead of 3, the width would have come out at 8.2 in — the same flow needing nearly twice the opening for a third less depth.

Result interpretation

The width is per opening, not in total. Three scuppers at 4.44 in pass the same flow as one at 13.3 in, and they keep working when one blocks.

The governing line tells you what to change. If the practical minimum governs, the opening is already as small as it should be and the hydraulics are not the problem. If the hydraulic width governs, the head or the count is the lever.

Worked examples: two scuppers and four

Example 1 — 6,000 sq ft through two scuppers

Peak flow
0.95 × 4 × 6,000 × 0.01039 = 236.9 gpm
Per scupper
236.9 ÷ 2 = 118.4 gpm
In cfs
118.4 ÷ 448.831 = 0.2639 cfs
Head
4 in = 0.3333 ft, so H1.5 = 0.1925
Width
0.2639 ÷ (3.0 × 0.1925) = 0.4571 ft
In inches
0.4571 × 12 = 5.5 in
Practical minimum
4.0 in — exceeded, so 5.5 in governs
width = 0.2639 ÷ (3.0 × 0.1925) = 0.457 ft = 5.5 in

Example 2 — the same roof through four scuppers

Per scupper
236.9 ÷ 4 = 59.2 gpm
In cfs
0.1320 cfs
Width
0.1320 ÷ 0.5774 = 0.2286 ft
In inches
2.7 in
Practical minimum
4.0 in — now governs
Governing width
4.0 in each, four openings

Four openings are hydraulically over-provided at the practical minimum width, which is the right outcome: the redundancy matters more than the exact area, and each opening is wide enough to stay clear.

width = 0.1320 ÷ 0.5774 = 0.229 ft = 2.7 in, raised to 4.0 in

The opening, the debris and the roof that sets the head

The width is one dimension of one detail. What surrounds it decides whether the number means anything.

The opening

A scupper is usually a rectangular slot through a parapet, with an invert at roof level and a soffit above. Its height matters as well as its width: a wide, shallow slot carries less than the same area in a taller opening, because the head is limited by the top.

The edge shape is where the coefficient comes from. A sharp, thin edge is the 3.0 case; a rounded or flared inlet carries more and can justify a higher figure. The opening also needs a lintel or a head detail above it, which is a structural item rather than a hydraulic one.

Water discharging through a scupper opening in a parapet wall, falling clear of the wall below.
The opening discharges into air. A scupper that discharges into a surcharged gutter behaves as an orifice, not a weir.

Debris

A scupper is the detail on a roof most likely to collect leaves, because it is a horizontal slot at the lowest point where water and debris arrive together. Screens help and also reduce the open area; a screen sized as if it were an opening will not pass the flow.

This is the argument for more, smaller openings rather than one large one. Several scuppers each carry a share, and a blockage in one raises the head rather than stopping the drainage.

The gravel stop and the upstand

The head is set by whatever the water must not reach, and on a ballasted roof the gravel stop is often the first of those. Its height above the roof surface is the real head, not the parapet's. The roof gravel stop calculation covers the edge detail and the ballast it retains.

The roof that sets the head

Where the roof is being re-laid, the insulation and the falls decide how deep water can stand before it reaches the scupper. A tapered scheme can raise the level at the parapet, and the tapered insulation calculation works out the depths that produces.

Where a flat roof is being converted to a pitched one, the parapet and its outlets change entirely, and the flat-to-pitched conversion calculation covers that change of arrangement.

Where the water goes next

A scupper discharges over or through the parapet, usually into a box gutter or straight to the ground. Where the roof instead drains through an internal outlet, the opening behaves as an orifice rather than a weir and the flat roof drain calculation is the relevant one.

Limitations and assumptions

What the calculation assumes

  • A sharp-edged weir. The coefficient of 3.0 suits a thin, square-edged opening; a rounded or flared inlet differs.
  • A free discharge. The opening is assumed to discharge into air, not into a surcharged gutter or a downpipe.
  • A plan area catchment. The area entered is assumed to be the horizontal projection.
  • An even split. Every scupper is assumed to take an equal share, which depends on the roof falls.
  • A clear opening. No screen, guard or debris is modelled.

What it does not include

  • Structural design of the opening. The lintel, the parapet strength and the flashing detail are separate.
  • Screen and guard losses. A screen reduces the effective area, and none of that is accounted for.
  • What happens downstream. The gutter, downpipe or ground the scupper discharges to is a separate calculation.
  • Ponding load. The structural effect of the head you allow is not checked here.
  • Overflow provision. A second, higher outlet is a separate design decision and is not modelled.

The result is the width one opening needs at the head you specified, or the practical minimum if that is larger. It is not a parapet detail, and it does not confirm the roof structure can carry the water depth it assumes.

Frequently asked questions

A scupper is an opening through a parapet or a wall at roof level, letting water leave sideways. A roof drain is an outlet in the roof surface itself, feeding a leader inside the building. A scupper is open to the air and behaves like a weir; a drain behaves like an orifice. They are sized with different equations, which is why this page exists separately.

Because a scupper is a weir, and weir flow rises with the depth of water above the invert to the power of one and a half. Doubling the head does not double the flow — it multiplies it by about 2.83. So a deeper body of water behind the same opening carries disproportionately more, and a wider opening is the linear way to add capacity.

It bundles the shape of the opening, the edge profile and the approach conditions into one number. A sharp-edged opening, a rounded one and a short throat all behave differently. Typical values sit around 3.0 in US customary units for a sharp-edged suppressed weir. Because the right value depends on the detail, it is an input rather than an assertion.

Because hydraulics and maintenance disagree. A scupper that is hydraulically sufficient at 2 in wide will block the first time a leaf arrives. The calculator reports the hydraulic width and the practical minimum, and takes the larger as the governing figure. That is the width to build.

The depth the roof can safely hold before water reaches a door threshold, a rooflight upstand or the top of the parapet flashing. That is a building-specific figure. It is not a hydraulic constant, and this page does not invent one.

No. It assumes a clear opening. In practice scuppers collect leaves and silt, which is one reason a design with several openings beats one large one. Two scuppers that each carry half the flow still work when one is blocked. A single opening sized for the whole flow does not.

Both start from the same peak flow. The gutter size calculator turns flow into an outlet count for a gutter run; this page turns the same flow into an opening width in a wall. If a roof discharges through scuppers into a gutter, calculate both: the scupper passes the water out, and the gutter carries it away.

Usually at or very slightly below the finished roof surface, so water can reach it. Sitting it above the surface creates a pond that never drains. The invert height is a detailing decision; this page sizes the opening once you have decided where the water level will sit.

Because each opening only carries its share, and the roof does not necessarily deliver flow evenly to all of them. Dividing evenly is the standard simplifying assumption. Where one scupper clearly serves a much larger area, size that one on its own share instead.

It can be impractical. A very wide opening in a parapet is a structural and aesthetic problem, and it may need a lintel or a frame. Adding openings is usually easier than widening one, and it also gives the redundancy that debris makes necessary.

Where these numbers come from

The flow calculation is the rational method and the opening calculation is the rectangular weir equation, both standard in drainage design. The unit constants are arithmetic.

The weir coefficient is an input because the correct value depends on the edge detail, and no single figure applies to every scupper. A value near 3.0 in US customary units is typical for a sharp-edged suppressed weir.

  • How codes treat scuppers. IPC 2021, Chapter 11 — Storm Drainage covers parapet wall scuppers in Section 1106.5: they are sized to prevent ponding beyond the design depth, with a minimum opening height of 4 inches, and a width not less than the circumference of a roof drain sized for the same area. That is the origin of the practical minimum this page applies.
  • Local plumbing or building drainage requirements, which may specify a design rainfall intensity and a method for sizing roof outlets.
  • Manufacturer data for proprietary scupper and overflow outlets, which is more reliable than a generic coefficient where a product is being installed.
  • Local rainfall intensity data for the design storm.

Discharging into a box gutter?

Check the channel can carry what the scupper delivers.