Gutter Size Calculator
Work out the peak flow a roof delivers in a storm, and how many outlets it takes to carry it. Enter the plan area draining to the run, a local rainfall intensity and the capacity of the outlet you intend to fit; the result is the flow, the outlet count and the spare capacity left over. It stops at the flow — the gutter profile itself comes from the manufacturer's table.
Quick answer: 1,200 sq ft of plan area at 4 in/hr with a runoff coefficient of 0.95 produces about 47.4 gpm. At 30 gpm per outlet that needs two outlets, each serving 600 sq ft, and leaves 21% of the installed capacity spare. Both rates are inputs: the intensity comes from local rainfall data, the capacity from the manufacturer.
- Plan area catchment
- Local rainfall intensity
- Outlets from flow
Gutter size calculator inputs and results
Use the plan area draining to the run; the sloped area overstates flow by the pitch factor.
Take the intensity from a local drainage authority or design chart. It is the assumption that changes the answer most.
From the manufacturer's outlet capacity table. The default is a placeholder, not a specification.
The count is peak flow divided by outlet capacity, rounded up; spare capacity shows how much margin remains.
Show calculation
Gutter sizing starts with a flow, not a width
Gutter sizing starts with a flow rate, not a width. The catchment collects rain, the intensity tells you how hard it falls, and the product of the two is the peak volume per minute that the drainage has to carry.
This page converts that flow into a number of outlets at a capacity you supply. It does not choose a gutter profile; that comes from the manufacturer's table once you know the flow.

The four inputs and five results
Four fields go in. Two describe the roof and the weather, one describes how much rain becomes runoff, and one describes the outlet you intend to use.
| Input | Unit | What it is | How to obtain it |
|---|---|---|---|
| Roof catchment | sq ft | Plan area draining to this run | Measured from the roof plan, not from the sloped surface |
| Rainfall intensity | in/hr | Design storm rate for the site | A local drainage authority or design chart for the applicable return period |
| Runoff coefficient | — | Share of rainfall that becomes runoff | 0.95 for a normal impervious roof; lower for a planted or porous covering |
| Capacity per outlet | gpm | What one outlet can pass | The manufacturer's outlet capacity table — the default here is a placeholder |
All four are entered on the left of the calculator, and the result updates as you type.
The five results
Two describe the water, two describe the outlets, and one is the margin between them.
| Result | Unit | What it means |
|---|---|---|
| Peak flow | gpm | What the catchment delivers at that intensity. A property of the roof and the weather, not of the gutter. |
| Outlets required | count | Peak flow divided by outlet capacity, rounded up. |
| Area per outlet | sq ft | Catchment divided by outlets — the roof area each one serves. |
| Capacity supplied | gpm | Outlets multiplied by capacity per outlet, after rounding up. |
| Spare capacity | % | How much of the installed capacity is not used by the design flow. |
Spare capacity is the margin against a blocked outlet or a leaf guard. A count that just clears the flow leaves none.
Which roof area drains to this run
The catchment is a plan area, and deciding which plan area belongs to this gutter is the part that changes the answer.
Plan area, not surface area
Rain falls vertically, so the volume a roof intercepts is set by its horizontal projection — the footprint, not the sloped surface of the covering. A steep roof does not collect more rain than the same footprint at a shallow pitch.
That means the sloped area from a roof takeoff overstates the flow by the pitch factor. If all you have is the sloped figure, divide it by 1.118 at 6:12, 1.250 at 9:12 or 1.054 at 4:12 before entering it.
Splitting a roof between runs
On a gable, each eave collects the plane behind it, so a roof draining to both sides gives half to each run. On a hipped roof the hips divide the planes, and each eave collects only the area behind it.
For a simple hipped or gabled roof the share is proportional to eave length: add the total eave length, then give each run its own length divided by that total. A square hip roof splits into four equal quarters; a rectangular one gives the two long eaves more than the two short ones.
Two things break that rule: cross-gables that create valleys, and dormers. In both cases water is diverted sideways, and the split has to be judged from the roof plan rather than calculated from eave lengths.
Measuring the plan area
Measure the footprint of the contributing planes and add them. On a rectangular building that is length by width for each section; on an L-shape it is two rectangles. The roof area calculation converts between footprint and sloped surface if you have one and need the other.
Common measurement mistakes
- Sloped area entered as catchment. It overstates the flow by the pitch factor — about 12% at 6:12.
- Whole roof given to one run. A gable draining both ways puts half its area on each eave.
- Dormers and cross-gables ignored. They divert water sideways and break the eave-length rule.
- Overhangs left out. The roof extends past the wall, and that water still arrives at the gutter.
- Two elevations added together. A roof discharging to separate runs is calculated run by run.
How to use the Gutter Size Calculator
Four fields, and the last one is the only one you have to look up in a product table.
- Enter the plan area draining to this run. If both sides of a gable drain to the same gutter, add both.
- Enter the rainfall intensity for your location, from a local design source.
- Leave the runoff coefficient near 0.95 for a normal roof; lower it for a planted or porous covering.
- Enter the outlet capacity from the manufacturer's table for the outlet you intend to use.
Read the outlet count, then check the flow against the profile capacity. This page stops at the flow; the profile is chosen from the manufacturer's table once you know it.
How the flow and the outlet count are worked out
The rational method, in US units.
outlets = ⌈ flow ÷ capacity per outlet ⌉
area per outlet = catchment ÷ outlets
capacity supplied = outlets × capacity per outlet
spare = (capacity supplied − flow) ÷ capacity supplied
Variables
- C
- Runoff coefficient — the share of rainfall that becomes runoff, dimensionless.
- I
- Rainfall intensity for the design storm, in inches per hour.
- A
- Catchment plan area draining to this run, in square feet.
- capacity per outlet
- Flow one outlet passes, in gallons per minute.
- outlets
- Whole outlets needed, rounded up.
- spare
- Unused share of the installed capacity, as a percentage.
Unit explanation
The constant converts a depth of rain over an area into a volume per minute. One square foot receiving one inch per hour is 1/12 cubic foot per hour, which is 0.01039 US gallons per minute.
Everything downstream is a count or a percentage, so there is no further conversion. That is why the catchment has to be in square feet of plan area: the constant is defined for a horizontal surface receiving vertical rain.
Why the catchment is plan area
The rational method's area is the horizontal projection of the draining surface, because rain arrives vertically. A roof at 9:12 has about 25% more surface than its footprint and collects exactly the same volume as that footprint would.
This is the single most common way the flow comes out too high. A takeoff gives sloped area, and entering it directly inflates the flow by the pitch factor — which then inflates the outlet count with it.
Why the count is rounded up
Partial outlets do not exist. A flow of 47.4 gpm against 30 gpm outlets needs 1.58 outlets, and the answer is two.
Rounding up is also what creates the spare capacity figure: two outlets supply 60 gpm for a 47.4 gpm flow, leaving 21% unused. That margin is the only thing standing between the design and a blocked outlet or a leaf guard.
Numerical example
2,400 sq ft of plan area at 5 in/hr with a coefficient of 0.9 and 40 gpm outlets:
- Peak flow
- 0.9 × 5 × 2,400 × 0.01039 = 112.2 gpm
- Outlets
- ⌈112.2 ÷ 40⌉ = ⌈2.81⌉ = 3
- Area per outlet
- 2,400 ÷ 3 = 800 sq ft
- Capacity supplied
- 3 × 40 = 120 gpm
- Spare capacity
- (120 − 112.2) ÷ 120 = 6.5%
Three outlets clear the flow but leave only 6.5% in hand. One more would take the margin to 30%, which is the practical argument for rounding up beyond the arithmetic rather than to it.
Result interpretation
The outlet count is what the flow requires, not what the gutter profile requires. The profile is a separate capacity check from the manufacturer's table, and a run can pass this test and still overflow if the channel is too small.
Spare capacity is the number to look at when the count lands just above a whole outlet. A result of 6% is a design that works on paper and is uncomfortable in a storm.
Worked examples: 4 in/hr and 6 in/hr
Example 1 — 1,200 sq ft at 4 in/hr
- Flow
- 0.95 × 4 × 1,200 × 0.01039 = 47.4 gpm
- Outlets at 30 gpm
- 47.4 ÷ 30 = 1.58 → 2
- Area per outlet
- 1,200 ÷ 2 = 600 sq ft
- Capacity supplied
- 2 × 30 = 60 gpm
Example 2 — the same roof at 6 in/hr
- Flow
- 0.95 × 6 × 1,200 × 0.01039 = 71.1 gpm
- Outlets at 30 gpm
- 71.1 ÷ 30 = 2.37 → 3
- Area per outlet
- 1,200 ÷ 3 = 400 sq ft
Fifty percent more rain needs fifty percent more outlets. This is why a design intensity from another region produces the wrong answer even when the roof is identical.
Outlets, profiles and what limits the run
This page returns a flow and a count. The parts that have to carry it are chosen separately, and each has its own limit.
The outlet
The outlet is usually the smallest opening in the system and therefore the part that governs. Its capacity comes from the manufacturer's table at a stated head of water, and outside those conditions it is an estimate.
Adding an outlet is nearly always cheaper than enlarging the profile on a long run, and it also shortens the distance water has to travel along the channel to reach one.

The profile
The gutter profile has its own capacity, and it is a separate check. A run can pass the outlet test and still overflow if the channel is too small for the flow it carries between outlets — which is why the flow from this page is the input to a profile table rather than the answer on its own.
Where the run is a box formed at roof level rather than a hung profile, the arithmetic is different, and the box gutter calculation checks it as an open channel.
Once the profile is chosen the run still has to be ordered, and the gutter run length calculation turns the measured runs into stock sections, joints and fittings.
The fall
Capacity assumes the water reaches the outlet. A gutter laid level or back-falling holds water along its length, so the flow this page returns never arrives. The gutter slope calculation gives the drop along the run and the height at the outlet.
Fixing and guarding
The run has to be held at the spacing the profile requires, and a run that sags creates the low point that holds water. The hanger spacing calculation gives the count of fixings for the run.
A leaf guard changes the effective opening, so a guarded gutter has less margin than the unguarded figure suggests. The guard calculation prices the covering, and it is worth reading the section on what a guard does not do before relying on it to keep the flow path clear.
Limitations and assumptions
What the calculation assumes
- The intensity is yours. The default is a placeholder for demonstration, not a design value for any location.
- Steady-state flow. The rational method assumes the storm lasts long enough for the whole catchment to contribute.
- Plan area catchment. The area entered is assumed to be the horizontal projection, not the sloped surface.
- An even split. Every outlet is assumed to take an equal share, which depends on the falls along the run.
- Single run. A roof draining to several separate runs is calculated run by run.
What it does not include
- The profile size. It gives the flow; the profile capacity comes from the manufacturer's table.
- Fall and outlet losses. Bends, long runs and level gutters all reduce real capacity.
- The pipe below. Downspouts, leaders and any underground connection are separate quantities.
- Condition of the existing system. Where the gutter is being replaced rather than designed, the gutter inspection calculation comes first.
- Cost. Flow and outlet count are not prices; the gutter cost calculation turns a run and its fittings into money.
The result is the flow a catchment delivers and the number of outlets needed to take it. It is not a gutter design, and it is not a statement that the installed system will not overflow in a storm larger than the design event.
Frequently asked questions
Two things have to carry the water: the gutter profile and the outlets. This calculator works out the peak flow from the catchment and the number of outlets needed at a given downspout capacity. Once you know the flow, compare it with the manufacturer's capacity table for the profile you intend to use. Gutter capacity is published per profile and per outlet configuration, and it changes with the number of outlets.
Because rain falls vertically. The amount of water a roof collects is set by the area it covers when seen from above, not by the longer sloped surface. Using the sloped area overstates the flow, sometimes by 40% on a steep roof, and leads to over-sized drainage.
The design intensity for your location, usually published by the drainage or building authority as a one-in-something storm for a short duration. It is not the average annual rainfall. Intensity is the single biggest assumption here. A figure for a different region will change the answer substantially, so take it from a local source rather than a default.
It is the share of rainfall that becomes runoff rather than being absorbed, evaporated or held. A hard roof is close to 1.0; a planted roof is much lower. 0.95 is a reasonable figure for an impermeable roof covering, which is why it is the default here.
It depends on the size, the head of water above the outlet, the number of bends and whether the outlet runs full. Manufacturers publish capacity tables for their outlets. The calculator asks for the capacity rather than assuming one, because a 3 in by 4 in outlet and a 4 in round outlet are not interchangeable.
Yes. A gutter laid to fall drains faster and self-cleans better than a level one. Standing water reduces the effective capacity and eventually causes overflow at the low point. Fall is a installation requirement, not something this calculator can size, but a gutter that holds water will underperform whatever number comes out here.
If the run is long, adding an outlet usually solves the problem more effectively than increasing the profile, because it halves the length of gutter each outlet has to serve. If the flow is high but the run is short, a larger profile or larger outlet may be the better answer. The peak flow figure tells you which constraint you are dealing with.
The catchment field accepts square metres and converts internally. Rainfall intensity is in inches per hour and outlet capacity in US gallons per minute. If your data is metric, convert the intensity (mm/hr to in/hr is divide by 25.4) and the capacity (litres per second to gpm is multiply by 15.85) before entering it.
Because a half outlet does not exist. If the flow needs 1.6 outlets' worth of capacity, you install two. The per-outlet catchment shown underneath is the practical check: it tells you the area each outlet is actually serving.
Where these numbers come from
The flow calculation is the rational method, a standard approach for estimating peak runoff from a small catchment. The only fixed element is the unit conversion from rainfall depth over an area to gallons per minute.
Rainfall intensity, runoff coefficients and outlet capacities are local or product data and are left as inputs for that reason.
- The rational method and the design storm. FAA Advisory Circular 150/5320-5C, drainage chapters (PDF, 667 KB) sets out the Rational Method, the runoff coefficient, and the use of an intensity–duration–frequency curve to pick the intensity — which is the calculation this page performs.
- Rainfall intensity. Local drainage authority or building department design intensities. For sites in the United States, NOAA's Precipitation Frequency Data Server publishes the underlying estimates.
- Outlet capacity. Gutter and downspout manufacturer capacity tables, which vary with profile, outlet size and head.
- Runoff coefficients. Published coefficients for roof surfaces; the value is left as an input for that reason.
This page estimates peak flow. It does not certify a drainage design or replace a local plumbing or drainage requirement.