R-Value Calculator
An R-value is a thermal resistance, and resistances add when the layers sit one behind the other. The R-value calculator turns up to three layers of thickness and R per inch into a layer R each and a total, and reports the U-value the assembly amounts to.
Quick answer: 6 in of insulation at R-3.5 per inch is R-21, and 2 in of board at R-5 is R-10. Together the assembly is R-29, which is a U-value of 0.034.
- Up to three layers
- R per inch by material
- Total R and U
Inputs and results
Leave the third layer at zero if it is not used. R per inch comes from the product data: about 3.5 for a batt, 5 for XPS, 6 for polyiso, 1.25 for timber.
Each layer R is its thickness times its R per inch, and the total is the sum. The U-value under the total is one divided by it.
Show calculation
What the R-value calculator works out
R is thermal resistance, measured in h·ft²·°F/BTU, and it adds when layers sit one behind the other. The R-value calculator takes up to three layers, turns each thickness and R per inch into a layer R, and sums them into a total.
It also reports the U-value, which is one over the total. That is the figure the roof heat loss calculation and any energy model actually use, and it is easy to forget that a high R is a low U rather than a big number on its own.
What it does not do is account for the framing, the surface films or the way heat moves sideways through a real assembly. Those are separate corrections, and the thermal bridging calculation is where the largest of them is worked out.

The six inputs and four results
Three pairs of fields, one pair per layer, and a layer you do not need stays at zero.
| Input | Unit | What it is | How to obtain it |
|---|---|---|---|
| Layer thickness | in | The depth of that layer as installed | Measured, or the product thickness |
| R per inch | h·ft²·°F/BTU per in | What one inch of the material is worth | The product data sheet |
All six are entered on the left of the calculator, and the result updates as you type.
The four results
One is the total, three are the layers, and the U-value sits under the total.
| Result | Unit | What it means |
|---|---|---|
| Total R-value | h·ft²·°F/BTU | The sum of the layer resistances. |
| Layer R | h·ft²·°F/BTU | Thickness times R per inch, for each layer. |
| U-value | BTU/h·ft²·°F | One over the total R, shown beneath the headline figure. |
The layer figures are there to be checked: if one of them looks wrong, the total is wrong for a reason you can find.
R per inch, by material
R per inch is the only input that describes the material, and it varies by a factor of five across the products used in a roof.
| Material | R per inch | Depth for R-30 |
|---|---|---|
| Fiberglass batt | 3.2 | 9.4 in |
| Mineral wool batt | 3.8 | 7.9 in |
| Cellulose, blown | 3.5 | 8.6 in |
| Fiberglass, blown | 2.5 | 12.0 in |
| EPS board | 3.8 | 7.9 in |
| XPS board | 5.0 | 6.0 in |
| Polyiso board | 6.0 | 5.0 in |
| Closed-cell foam | 6.2 | 4.8 in |
| Open-cell foam | 3.7 | 8.1 in |
| Softwood framing | 1.25 | 24.0 in |
| Gypsum board | 0.9 | 33.3 in |
Typical published values. Products within a type vary, and the data sheet always wins over the table.
Two things follow. The depth needed for a given R varies by more than a factor of two across the soft insulations, which is why a shallow rafter forces a denser product. And the structural layers contribute almost nothing: an inch of timber is worth R-1.25 against R-6 for an inch of foam.
The thickness
Use the thickness as installed. A batt squeezed into a shallow rafter is thinner than its label and worth less R, and loose fill settles over the years.
Where the layer is not flat — over a textured surface, or between rafters with a sagging batt — the effective thickness is less than the nominal one.
The layers
Three fields are enough for most assemblies: insulation, sheathing, and a lining. Where there are more, combine two similar layers into one with an area-weighted R per inch, or run the calculator twice and add the totals.
Layer order does not matter to the arithmetic. It matters a great deal to the moisture performance, which is why the moisture barrier calculation cares where each layer sits.
Common measuring mistakes
- Total thickness entered as R. A thickness of 6 in is not R-6; it is R-21 at 3.5 per inch.
- Nominal thickness used for a compressed batt. Overstates the R.
- R per inch taken from a different product. Two fiberglass batts can differ by 15%.
- Framing left in as if it were insulation. It is a parallel path, not a series layer.
- The total read as the assembly R. Bridging and films still have to be applied.
How to use the R-value calculator
Six fields, and a layer you do not have stays at zero.
- Enter the first layer's thickness and R per inch. Usually the insulation.
- Enter the second layer. Sheathing, board or lining.
- Enter the third, or leave it at zero.
Then check the layer figures against what you expect: if the insulation is 6 in at 3.5 per inch, layer one should read 21, and if it does not, one of the two fields is wrong.
The arithmetic: layer R and total R
total R = R₁ + R₂ + R₃
U-value = 1 ÷ total R
Variables
- thickness
- The installed depth of the layer, in inches.
- R per inch
- The material's resistance per inch, from its data sheet.
- layer R
- That layer's resistance, in h·ft²·°F/BTU.
- total R
- The sum of the layers, which is the assembly's resistance.
Unit explanation
R per inch carries the unit of R divided by inches, so multiplying by a thickness in inches returns an R. That is why the two fields have to be consistent: inches with R per inch, not millimetres with R per inch.
The U-value is a conductance, so it is one over the resistance. It carries BTU/h·ft²·°F, which is the unit a heat loss calculation multiplies by area and temperature difference.
Why resistances add
Heat crossing several layers meets each one in turn, so the same flux passes through all of them and the temperature drops are what add. That makes the resistances additive and the conductances not.
It is the opposite of the parallel case, where the layers sit side by side and the conductances add instead. The framing in a roof is parallel, which is why it is not entered here.
Why the U-value is reported
Because R is a design figure and U is an engineering one. A specification says R-38; a heat loss calculation needs 0.026, and the conversion is the step where mistakes happen.
Reporting it under the total means the reader does not have to remember whether to invert, and it keeps the two figures visible together.
Numerical example
6 in of insulation at R-3.5 per inch, plus 2 in of board at R-5 per inch:
- Layer 1
- 6 × 3.5 = 21.0
- Layer 2
- 2 × 5.0 = 10.0
- Total R
- 21.0 + 10.0 = 31.0
- U-value
- 1 ÷ 31.0 = 0.032
The same total in a lower-density product would need more depth: 31 divided by 2.5 per inch is 12.4 in, against 6.2 in of closed-cell foam.
Result interpretation
The total is the resistance of the layers you entered, in series, without the surface films and without the framing. It is the number a specification is written against, and the number to compare products by.
What it is not is the assembly's performance. That needs the bridging discount and, for a heat loss figure, the films, and the two together can take a nominal R-38 down to an effective R-30 or lower.
Worked examples: a batt with board, and two rigid layers
Example 1 — mineral wool and XPS
Inputs: 6 in at R-3.8, 2 in at R-5.0, third layer zero.
- Layer 1
- 22.8
- Layer 2
- 10.0
- Total R
- 32.8
- U-value
- 0.030
A familiar build-up: a full cavity of mineral wool with a rigid board over the rafters. The board does two jobs, adding R and breaking the bridging that the wool between the rafters cannot.
Example 2 — two rigid layers
Inputs: 4 in at R-6.2, 2 in at R-6.0, third layer zero.
- Layer 1
- 24.8
- Layer 2
- 12.0
- Total R
- 36.8
- U-value
- 0.027
More R in half the depth of the first example, because both products are dense. That is the trade a shallow rafter forces: pay for density, or lose the R.
Series, parallel and the films
This calculator handles the series case. Two other effects decide whether the total is what the roof actually delivers.
The surface films
Still air against a surface resists heat too: about 0.61 on the inside and 0.25 on the outside, roughly 0.86 in total. They are in series with the layers and are usually added to the assembly R rather than to the insulation R.
They matter most on a thin assembly, where they are a large share of the total, and least on a deep one.
The framing
Rafters and joists sit beside the insulation rather than in series with it, so they are a parallel path and cannot be added as a layer. Their effect is to reduce the effective R, and the thermal bridging calculation is where the discount is applied.
Entering a rafter as a fourth layer would be wrong in both directions: it would add resistance where the framing actually removes it.
Compression and gaps
A batt compressed to fit delivers less than its nominal R, and a batt with gaps around it delivers less again because air circulates. Neither shows up in the arithmetic, and both are common.
The rule is to buy a product that fits the depth rather than one that has to be squeezed, which is the cathedral ceiling calculation's subject.
Where the total goes next
The total R becomes a U-value, the U-value becomes a heat loss, and the heat loss becomes a bill. The heat loss calculation is the next step.
The insulation calculator works the other way, from a target R to a thickness.

Limitations and assumptions
What the calculation assumes
- Layers in series. The assembly is one-dimensional, with each layer covering the whole area.
- No framing. Parallel paths through rafters and joists are not included.
- No surface films. The still-air resistances either side are outside the total.
- Nominal thickness. The layers are assumed to be at their stated depth, uncompressed and gap-free.
- Three layers. More than three needs either a combined layer or two runs added together.
What it does not include
- Thermal bridging. Usually the largest correction, and always a reduction.
- Air movement. Circulation through and around the insulation reduces performance.
- Temperature effects. Conductivity varies with temperature, and foam in particular drifts with age.
- Moisture. Wet insulation performs far worse than dry.
- Heat loss. The U-value is the input to that calculation, not the answer.
The result is the series resistance of up to three layers. It is the figure specifications are written in, and the starting point for everything else.
How thickness and R per inch behave
The total is a product of thickness and R per inch, so doubling either doubles the layer R. That makes the arithmetic easy to check and easy to get wrong by a factor of two.
| Thickness at R-3.5 | Layer R | U-value | Note |
|---|---|---|---|
| 3 in | 10.5 | 0.095 | A shallow rafter |
| 6 in | 21.0 | 0.048 | An older ceiling |
| 9 in | 31.5 | 0.032 | A modern ceiling |
| 12 in | 42.0 | 0.024 | A deep ceiling |
Single layer, no films, no framing. The U-value falls as the R rises, which is the relationship the page's headline shows.
R per inch does the same job from the other side, and it is where the products differ most: the same 6 in is R-15 in a low-density batt and R-37 in closed-cell foam.
| Material | R per inch | R in 6 in | Depth for R-38 |
|---|---|---|---|
| Fiberglass, blown | 2.5 | 15.0 | 15.2 in |
| Fiberglass batt | 3.2 | 19.2 | 11.9 in |
| Cellulose | 3.5 | 21.0 | 10.9 in |
| XPS board | 5.0 | 30.0 | 7.6 in |
| Polyiso board | 6.0 | 36.0 | 6.3 in |
Typical values. The last column is the depth each material needs to reach the same target, which is the practical difference between them.
Read together, the tables say that R is bought either with depth or with density, and that the choice is usually made by the space rather than by the price.
Frequently asked questions
Thermal resistance: how much a material or assembly slows the flow of heat for a given temperature difference, in h·ft²·°F/BTU. Higher is better, and resistances add when layers sit one behind the other.
From the product data sheet, or by dividing the quoted R by the thickness. A batt rated R-21 at 6 in is 3.5 per inch; a board rated R-10 at 2 in is 5 per inch. The table on this page gives typical values by material.
Because you have added layers. A 6 in batt at R-21 plus 2 in of board at R-10 is R-31, which is more than either label. The total is the assembly, and the labels are the parts.
Not to the arithmetic: resistances add in any order. It matters a great deal to moisture, because the vapour barrier belongs on the warm side and the drying path on the cold one. The moisture barrier calculation is where the order is decided.
No. The framing runs beside the insulation rather than in series with it, so it is a parallel path and adding it as a layer would add resistance where it actually removes it. The thermal bridging calculation applies the correct discount.
They add about 0.86 in total, 0.61 inside and 0.25 outside, and they are usually quoted with the assembly rather than with the insulation. On a deep ceiling they are a small share; on a thin assembly they matter more.
U = 1 ÷ R, so R-29 is U 0.034 and R-38 is U 0.026. The calculator shows it under the total, because the inversion is where most arithmetic errors happen.
Compression, gaps, settling, air movement and the framing all take a share. The label is a laboratory figure for a full, undisturbed thickness; the assembly is a set of layers with interruptions, which is why the effective R is always lower.
Where these numbers come from
Each layer R is its thickness times its R per inch, the total is the sum of the layers, and the U-value is one over the total. Nothing else is needed beyond the product data.
No R per inch or thickness is asserted here, because both come from the product being specified.
- The R per inch figures. ENERGY STAR — choosing the appropriate insulation type covers the product families, and the manufacturer's data sheet gives the figure for a specific product.
- The U-value relationship. Engineering Toolbox — overall heat transfer coefficient gives q = U·A·ΔT and states that R is one over U.
- The surface films. About 0.61 inside and 0.25 outside for a horizontal surface, which is the 0.86 usually added to an assembly R.
- The bridging discount. Not part of this total; the thermal bridging calculation applies it separately.
Checking the rafter depth?
The R has to fit in the space the structure leaves.