Roof Skylight Energy Calculator
A skylight is a small hole with a high U-value, and it loses far more heat per square foot than the roof around it. The roof skylight energy calculator turns the glazing area, its U-factor and the temperature difference into heat loss, loss per square foot and the fuel cost of replacing it.
Quick answer: 40 sq ft of double glazing at U 0.50 with a 50°F difference loses 1,000 BTU/h — 25 BTU/h per square foot, against about 1.3 for the R-38 ceiling beside it. Over 2,000 hours that is $28 of fuel at $12 per MMBtu and 85% efficiency.
- Glazing U-value
- Loss per square foot
- Conduction only
Inputs and results
U-factor comes from the NFRC label on the product: about 1.0 for single glazing, 0.5 for double, 0.20 to 0.30 for low-e double or triple.
Heat loss is conduction through the glazing and frame at the stated difference. The cost is that heat divided by the plant's efficiency and priced as fuel.
Show calculation
What the roof skylight energy calculator works out
A skylight is a small area with a poor U-value, and the two together decide what it costs. The roof skylight energy calculator takes the glazing area, the product's U-factor and the temperature difference, and returns the heat loss in BTU per hour, the same figure per square foot, and the fuel cost over a period.
The per-square-foot figure is the one that matters for a skylight, because it is what makes the comparison with the insulated roof beside it. At U 0.50 the glazing loses about twenty times as much heat per square foot as an R-38 ceiling does.
The calculation is conduction only. Sun through the glass is a separate gain, and it can be larger than the winter loss in a sunny climate — the roof heat loss calculation is the version for the roof around it.

The six inputs and three results
Three fields describe the skylight and the weather, one the period, and two the fuel.
| Input | Unit | What it is | How to obtain it |
|---|---|---|---|
| Glazing area | sq ft | The area of glass, not of the opening | The product size, or measured on the glass |
| Skylight U-factor | BTU/h·ft²·°F | How readily the unit conducts heat | The NFRC label or the product data |
| Temperature difference | °F | Indoor minus outdoor | A design condition, not a seasonal average |
| Hours in the period | h | How long the difference is held | 24 per day, times the days |
| Fuel rate | $ per MMBtu | What the fuel costs per million BTU | The bill, converted to MMBtu |
| Heating efficiency | 0–1 | How much of the fuel reaches the rooms | The appliance rating, for example 0.85 |
All six are entered on the left of the calculator, and the result updates as you type.
The three results
One is a rate, one is the same rate per square foot, and one is money.
| Result | Unit | What it means |
|---|---|---|
| Heat loss | BTU/h | Conduction through the glazing and frame at the stated difference. |
| Per sq ft | BTU/h·ft² | The intensity, which is what compares with the roof. |
| Cost for the period | $ | The heat divided by the efficiency, priced as fuel. |
The intensity is the number to quote: a skylight at 25 BTU/h·ft² is doing twenty times the work of the ceiling beside it.
Choosing the skylight U-value
The U-factor comes from the product label, and it is the only input that describes the skylight itself. The rest describe the house and the weather.
| Glazing | Typical U-factor | Heat loss at 40 sq ft, 50°F | Cost over 2,000 h |
|---|---|---|---|
| Single glazed | 1.00 | 2,000 BTU/h | $56 |
| Double, clear | 0.50 | 1,000 BTU/h | $28 |
| Double, low-e | 0.30 | 600 BTU/h | $17 |
| Triple, low-e | 0.20 | 400 BTU/h | $11 |
| R-38 roof, for comparison | 0.026 | 52 BTU/h | $1 |
Typical values; the NFRC label on the product is the figure to use. Fuel at $12 per MMBtu and 85% efficiency.
Two things follow. A single-glazed skylight costs five times what a triple-glazed one does for the same opening, which is usually more than the price difference between them. And even the best glazing is an order of magnitude worse per square foot than the roof, so the area is the other lever.
The area
Use the glass area rather than the rough opening: a skylight with a wide frame can have a quarter less glass than its nominal size suggests, and the frame is rated with the unit anyway.
Where there are several skylights, add their glass areas. Two 20 sq ft units behave exactly like one 40 sq ft unit for conduction.
The temperature difference and the hours
Use a design difference for the condition, and the hours that difference is held for. A 50°F difference is a 70°F room at 20°F outside; 2,000 hours is a long heating season of continuous cold.
Because the loss is proportional to the difference, a night at 0°F loses twice what a night at 35°F does through the same glass.
The fuel rate and efficiency
The rate is per million BTU of fuel: a therm of gas is 0.1 MMBtu, so $1.20 a therm is $12 per MMBtu. Efficiency is the seasonal rating of the plant, and above 1 for a heat pump.
The cost figure is the fuel to replace the heat, not the whole bill, so it is the skylight's share rather than the house's.
Common measuring mistakes
- Opening size used as glazing area. Overstates the area and the loss with it.
- Centre-of-glass U used for the whole unit. The frame is worse, and the label's U covers the unit.
- Seasonal average used as the design difference. Understates the peak loss.
- Gas price per therm entered as the MMBtu rate. Out by a factor of ten.
- Solar gain ignored. In a sunny climate it can offset the winter loss and then some.
How to use the roof skylight energy calculator
Six fields, and the U-factor is the one to take from the label rather than guess.
- Enter the glazing area. The glass, in square feet.
- Enter the U-factor. From the NFRC label on the product.
- Enter the temperature difference. Indoor minus outdoor for the design condition.
- Enter the hours. How long that difference is held.
- Enter the fuel rate. Per MMBtu, converted from the unit you buy.
- Enter the efficiency. The seasonal rating of the heating plant.
Then run it with a better glazing U and compare the cost figures. The difference is what the upgrade is worth over the period, before anything is said about daylight or summer heat.
The arithmetic: heat loss through a skylight
per square foot = U × ΔT
heat lost = heat loss × hours ÷ 1,000,000
fuel = heat lost ÷ efficiency
cost = fuel × fuel rate
Variables
- U
- The unit's U-factor from its label, in BTU/h·ft²·°F.
- area
- Glazing area in square feet.
- ΔT
- Indoor minus outdoor temperature, in °F.
- hours
- The period the difference is held for.
- efficiency
- Seasonal efficiency of the heating plant.
- fuel rate
- Price of fuel per million BTU.
Unit explanation
U times area times a temperature difference leaves BTU per hour. Dividing by the area again leaves U times ΔT, which is BTU/h per square foot — the intensity that makes a skylight comparable with a wall or a ceiling.
Multiplying the rate by hours gives BTU for the period, and dividing by a million converts it to MMBtu for the fuel price.
Why per square foot is the useful figure
A skylight is small, so its total loss looks modest next to a whole roof. The intensity shows the truth: at 25 BTU/h·ft² it is losing heat twenty times faster than the ceiling it interrupts.
That is also why the area matters so much: doubling the glazing doubles the loss, and the same 40 sq ft of skylight can undo a large area of insulation.
Why the frame is in the number
The U-factor on a skylight label covers the whole unit, frame included. A thermally broken frame with warm-edge spacers performs close to the glass; a metal frame without a break performs much worse, and the label captures that.
Centre-of-glass values are published by glass manufacturers and are always better than the unit figure. Using one understates the loss.
Numerical example
40 sq ft of double glazing at U 0.50, a 50°F difference, 2,000 hours, $12 per MMBtu and 85% efficiency:
- Heat loss
- 0.50 × 40 × 50 = 1,000 BTU/h
- Per square foot
- 1,000 ÷ 40 = 25 BTU/h·ft²
- Heat lost
- 1,000 × 2,000 ÷ 1,000,000 = 2.0 MMBtu
- Fuel
- 2.0 ÷ 0.85 = 2.35 MMBtu
- Cost
- 2.35 × $12 = $28
The same opening in single glazing costs twice as much, and in triple low-e less than half. The area did not change in any of them.
Result interpretation
The cost is the fuel to replace the heat over the period, and it is small in absolute terms because a skylight is a small area. What makes it worth attention is the intensity, and the fact that the same money spent on glazing usually buys more than the same money spent on more roof insulation.
It is also a winter figure. Summer solar gain through the same glass is a separate calculation, and it can be the larger of the two in a sunny climate.
Worked examples: double glazing and low-e
Example 1 — 40 sq ft of double glazing
Inputs: 40 sq ft, U 0.50, 50°F difference, 2,000 hours, $12 per MMBtu, 85%.
- Heat loss
- 1,000 BTU/h
- Per square foot
- 25 BTU/h·ft²
- Heat lost
- 2.0 MMBtu
- Cost for the period
- $28
Twenty-five BTU per square foot per hour is roughly what an uninsulated timber wall does. The ceiling beside it is doing 1.3, which is the whole argument for spending on the glazing before the insulation.
Example 2 — the same opening in low-e double
Inputs: 40 sq ft, U 0.30, 50°F difference, 2,000 hours, $12 per MMBtu, 85%.
- Heat loss
- 600 BTU/h
- Per square foot
- 15 BTU/h·ft²
- Heat lost
- 1.2 MMBtu
- Cost for the period
- $17
Forty per cent less heat for a coating on the same unit. The cost saving looks small in dollars because the area is small, but it is 40% of whatever the skylight was costing, and it compounds over the life of the unit.
Glazing, frames and the sun
The U-factor is a single number standing for several parts, and each of them can be the weak link.
The glazing
Single glass is about U 1.0, double about 0.5, and a low-e coating on double brings it to 0.3. The coating works by reflecting long-wave radiation back into the room, which is why it changes the U so much without changing the thickness.
Gas fill and warm-edge spacers take a well-made unit toward 0.2. Below that the frame becomes the limiting part, and the label reflects it.
The frame and the well
A metal frame without a thermal break conducts heat straight through, and the unit's U-factor will show it. A timber or thermally broken frame performs closer to the glass.
A deep shaft or well between the roof and the ceiling adds its own surface area and can add condensation risk, which is the skylight well depth calculation's subject.
Solar gain in summer
The same glass that loses heat in winter admits sun in summer, and the solar heat gain coefficient on the label is the number that governs it. A low SHGC keeps the summer gain down at the cost of some winter benefit.
In a cooling-dominated climate the summer gain can outweigh the winter loss entirely, which is why a skylight can be a net cost in one climate and a net benefit in another. The roof energy savings calculation covers the seasonal version of the heating side.
Condensation
A cold pane is a condensing surface, and the condensation resistance rating on the label says how well the unit resists it. Single glazing in a humid room will run with water on a cold night whatever the frame does.
That is a comfort and durability issue rather than an energy one, but it is usually what prompts the replacement, and the skylight replacement cost estimate is where the capital side is priced.
Daylight
The reason the skylight is there is light, not heat. Visible transmittance is the rating that measures it, and a low-e coating that blocks heat also blocks some light — which is the trade to check before choosing a unit on U-factor alone.

Limitations and assumptions
What the calculation assumes
- Steady state. The difference is held constant for the whole period, so a changing outdoor temperature is averaged into the input.
- One U-factor. The unit is uniform, with the frame included in the label figure.
- Conduction only. Solar gain, air leakage around the frame and thermal bridging at the curb are outside it.
- No shading. Blinds, trees and reveals that cut the sun are not modelled.
- A single indoor temperature. Zoned or setback heating is not represented.
What it does not include
- Summer solar gain. Often the larger term in a sunny climate, and the opposite sign.
- Air leakage. A poorly sealed skylight leaks air as well as heat.
- Thermal bridging at the curb. The frame around the opening is colder than the roof.
- Capital cost. No product or installation price is entered, so there is no payback here.
- Daylight benefit. The reason for the skylight is not in the arithmetic.
The result is the conduction loss of one glazed area over a stated period. It is the figure to compare units with, not a prediction of the bill.
How the numbers behave
Both the U-factor and the area enter linearly, so the loss is a product rather than a curve. The table below holds the area at 40 sq ft and the difference at 50°F.
| Glazing | U-factor | Heat loss | Per sq ft | Cost |
|---|---|---|---|---|
| Single | 1.00 | 2,000 BTU/h | 50 | $56 |
| Double, clear | 0.50 | 1,000 BTU/h | 25 | $28 |
| Double, low-e | 0.30 | 600 BTU/h | 15 | $17 |
| Triple, low-e | 0.20 | 400 BTU/h | 10 | $11 |
40 sq ft, 50°F difference, 2,000 hours, $12 per MMBtu, 85%. Per sq ft in BTU/h·ft².
Area does the same thing from the other side, and it is the lever that is easiest to get wrong: two skylights are twice the loss of one, and a large unit is worse than its glazing suggests.
| Glazing area | Heat loss | Cost | Equivalent R-38 roof |
|---|---|---|---|
| 10 sq ft | 250 BTU/h | $7 | 190 sq ft |
| 20 sq ft | 500 BTU/h | $14 | 380 sq ft |
| 40 sq ft | 1,000 BTU/h | $28 | 770 sq ft |
| 80 sq ft | 2,000 BTU/h | $56 | 1,540 sq ft |
U 0.50, everything else at the defaults. The last column is the ceiling area that would lose the same heat at U 0.026.
The last column is the one worth remembering: 40 sq ft of double glazing loses what 770 sq ft of well-insulated ceiling loses. A skylight is never a small energy decision, whatever its area.
Frequently asked questions
0.30 or better is a good modern unit, and 0.20 is available in triple glazing. The NFRC label gives the whole-unit figure, frame included, so it is the one to compare: a centre-of-glass value always looks better than the unit it belongs to.
Roughly twenty times as much per square foot. At U 0.50 the glazing loses 25 BTU/h·ft² at a 50°F difference, against about 1.3 for an R-38 ceiling. Forty square feet of skylight is therefore losing what 770 square feet of insulated roof loses.
It can, through solar gain on a sunny winter day, but the conduction loss runs all night and on cloudy days. Over a heating season the glass usually loses more than the sun gives back in a cold climate, and the daylight is the honest justification rather than the energy.
It is the other half of the story and it has the opposite sign. The solar heat gain coefficient on the label governs it, and in a cooling-dominated climate the summer gain can outweigh the winter loss. A low SHGC unit is the compromise, at the cost of some winter benefit.
Because the glass is the coldest surface in the room. A single-glazed unit will run with water on a cold night whatever else is done, and a better unit raises the surface temperature enough to stop it. The condensation resistance rating on the label is the figure to compare.
On energy alone, rarely: the fuel saving on 40 sq ft is tens of dollars a year. On condensation, draughts, failed seals and summer overheating, often yes. The replacement cost estimate is where the two sides are put together.
The glass, because that is where the U-factor applies. Using the rough opening overstates the loss by the width of the frame, which on a small unit can be a quarter of the area.
No. It is a conduction estimate for one glazed area at one condition. Air leakage, solar gain, thermal bridging at the curb and the daylight benefit are all outside it, and an assessment is where they are weighed together.
Where these numbers come from
The loss is the U-factor times the glazing area times the temperature difference, held for the hours entered. Per square foot is the same figure divided back by the area, and the cost divides the heat by the plant's efficiency before pricing it.
No U-factor, area or fuel price is asserted here, because all three describe a particular product and building.
- The U-factor and the other ratings. National Fenestration Rating Council certifies the energy performance of windows, doors and skylights, and its label carries the U-factor (0.20 to 1.20 for most products), the solar heat gain coefficient, visible transmittance and condensation resistance. That label is the source for the field on this page.
- The heat transfer equation. Engineering Toolbox — overall heat transfer coefficient gives q = U·A·ΔT, which is the whole of the arithmetic here.
- The fuel rate and efficiency. The utility bill and the appliance rating, converted to the units the fields ask for.
- The temperature difference. A design condition for the location, or a measured indoor and outdoor pair on the day being assessed.
Sizing the skylight?
The area is the second lever after the glazing, and the daylight is why it is there.